RMU

To share:

ELX24 series Eco-friendly Gas Insulated Ring Main Unit

  • ELX24 series Eco-friendly Gas Insulated Ring Main Unit-1
  • ELX24 series Eco-friendly Gas Insulated Ring Main Unit-2
  • Description
  • Specification
  • Features
  • Size
  • Catalogue

ELX24 series eco-friendly gas insulated ring main unit is characterized by reasonable design, reliable power supply, compact structure, easy for installation, flexible operation, small size and cost-effectiveness. It is applied in the distribution system of three-phase AC 50Hz, rated voltage 12kV, especially in power system of small secondary power distribution station, switching station, industrial and mining enterprises, urban residential area, airport, railway, tunnel, high-rise building, etc. to receive and distribute energy.


Standards

IEC 62271-102:2001     

IEC 62271-102A1:2011        

IEC 60265-1:1998       

IEC 62271-100:2008        

IEC 62271-200:2003        

IEC 60529:2001      

IEC 62271-1:2007

IEC 60060-1:2010   

IEC 60694-2002       

Main technical data of RMU

No

Description

Unit

Parameter

1

Rated voltage

kV

12

2

Power frequency withstand voltage

Phase to phase/earth

kV

42

Across the isolating distance

kV

48

3

Lightning impulse withstand voltage

Phase to phase/earth

kV

75

Across the isolating distance

kV

85

4

Rated frequency

Hz

50

5

Rated current

A

630

6

Rated short circuit breaking current

kA

20

7

Rated short time withstand current

kA/s

20/4

8

Rated peak withstand current

kA

50

9

Rated short circuit making current (peak)

kA

50

10

Resistance of main circuit

μΩ

140

11

Rated operating sequence

 

O-0.3s-CO-180s-CO

12

Mechanical endurance

VCB & LBS

Ops.

10000

ES with disconnector

3000

13

Electrical endurance

VCB breaking capacity

Ops.

30

LBS making capacity

100

ES making

2

14

Control voltage of auxiliary circuit

 

24, 48, 110, 220DC

110,220AC

15

IAC duration

s

0.5

16

Rated gas pressure (AP)

MPa

0.12

17

Annual gas leakage rate

 

0.02%

18

Protection degree

IP4X


Technical data of VCB unit

No.

Description

Unit

Parameter

1

Rated voltage

kV

12

2

Rated current

A

630

3

Rated frequency

Hz

50

4

Rated insulation level

Rated power frequency withstand voltage(Phase to phase/earth, across the isolating distance), 1min

kV

42/48

Rated lightning impulse withstand voltage (phase to phase/earth, across the isolating distance)

kV

75/85

5

Rated short time withstand current

kA

20

6

Rated short circuit duration

s

 

4

7

Rated peak withstand current

kA

50

8

Rated short circuit making current

kA

50

9

Rated short circuit breaking current

kA

20

10

Rated operating sequence

O-0.3s-CO-180s-CO

11

Mechanical endurance

Ops.

10000

Technical data of LBS unit

No.

Description

Unit

Parameter

1

Rated voltage

kV

12

2

Rated current

A

630

3

Rate frequency

Hz

50

4

Rated insulation level

Rated power frequency withstand voltage (phase to phase/earth, across the isolating distance), 1min

kV

42/48

Rated lightning impulse withstand voltage (phase to phase/earth)

kV

75/85

5

Rated short time withstand current

kA

20

6

Rated short circuit duration

s

4

7

Rate peak withstand current

kA

50

8

Rated short circuit making current

kA

50

9

Rated short circuit breaking current

kA

20

10

Rated operating sequence

O-15s-CO

11

Mechanical endurance

Ops.

10000










  • ELX24 is eco-friendly gas insulated, environmental friendly, pollution-free, compact design, its outline dimensions similar to SF6 RMU.
  • The RMU structure is classic design, comprising of instrument compartment, gas tank compartment, cable compartment and mechanism compartment. A pressure relief passage is arranged in cable compartment and gas tank compartment, to safeguard the equipment and personnel in case of internal arc fault. Mechanical interlocks are arranged between load break switch, circuit breaker, 3-position disconnector and cable compartment, with “five-proof” functions of switchgear.
  • The vacuum interrupters used in ELX24 RMU adopt CuCr contact material, of small electrical wear rate, long life span, high and stable insulating strength, rapid arcing recovery, high breaking capacity. The vacuum interrupters are embedded by APG process, to meet requirements for reliable performance and miniature design.
  • The disconnector of RMU is double blade design, so it has 2 isolating clearances, which has high breaking capacity than single isolating clearance, also solves the insulating saturation of arcing, thus to increase the reliability of equipment, to have better electrical performance and life span.
  • The ELX24 is modular design, the functional units are free to be combined and integrated.